Transmitter parameters
It contains additional transmitter parameters. The window layout depends on a transmitter type.
Below you can see a window containing settings of one of the transmitters.
- Long tag
- a message field for any content, cannot be longer than 24 characters.
- Inflection point
- relates to root characteristics. The range percentage from which this characteristics
is enabled. Below this value, the transmitter operates on the basis of own characteristics (cubic function).
- Product code
.
Restore factory settings:
Analog output configuration:
- Operation mode
- alarm limits depend on a selected mode:
- Normal
- standard alarm limits.
- Namur
- Namur-compliant alarm limits.
- Alarm current
- define current to be set in case of an transmitter failure (depends on Alarm at):
- High
- 22,0 mA current will be set.
- Low
- 3,6 mA current will be set.
- Output operation limit
- a read-only parameter, visible only for some transmitters.
- Alarm at
- select which module errors activate the transmitter’s alarm
Limits:
- Pressure
- Transmitter compensation limits
- Temperature
- permissible operating temperature.
Version information - software and transmitter electronics versions.
Content of fields, in which value can be entered, can be transfered to the transmitter with a command Write.
The command Read allows to read only those parameters, which are shown in the above window.
To read all transmitter parameters, you should use the command Read configuration.